Start Here
User Manual
2
To modify the WriteData array, follow the above steps, substituting WriteData
for ReadData.
3
Save and download the configuration to the module (page 61) and reboot.
Make sure that the ReadData and WriteData arrays do not overlap in the module
memory. For example, if your application requires 2000 words of WriteData
starting at register 0, then your Read Register Start parameter must be set to a
value of 2000 or greater.
Page 36 of 161