MVI56E-MNETCR ♦ ControlLogix Platform
Modbus TCP/IP Multi-Client Enhanced Communications Module for Remote Chassis
Block Request from Processor to Module
Word Offset
0
1 to 41
The module does not send a response block for this command.
Cold Boot Block (9999)
This block is equivalent to performing a hardware reset, and causes the module
to restart in the same way as if the power was cycled. The Cold Boot control
block also reloads the module's backplane and application port drivers, restarts
the program, and resets all internal registers to zero.
Note: In some cases, the read section of the module database (transferred from module to
processor) must keep its values after a reboot. To repopulate the module's registers with the last
values the module sent to the processor, set the Initialize Output Data parameter in the module
configuration to Y
Block Request from Processor to Module
Word Offset
0
1 to 41
The module does not send a response block for this command.
ProSoft Technology, Inc.
Description
9998
Spare
.
ES
Description
9999
Spare
Reference
User Manual
Length
1
41
Length
1
41
Page 119 of 161