2 USING THE E-MAIL FUNCTION
Initial normal completion signal
(X19)
MSEND
instruction
MSEND instruction
completion device
MSEND instruction
completion device + 1
(Normal completion/abnormal completion)
2 - 16
(1) Send using the sequence program
The following explains how an e-mail is sent using the sequence program.
See Chapter 6 MSEND for detail.
Direction
Send the e-mail
M10
M11
M11
(2) Execution timing of the instruction
Initial processing
1)
1) Start the local station programmable controller.
The parameters for the e-mail function are stored in the Ethernet module.
2) Execute the MSEND instruction.
The e-mail designated with the MSEND instruction is sent to the mail server.
3) When the e-mail sending to the send mail server is completed, the MSEND
instruction completion device turns on.
When the completion device + 1 (abnormal completion signal) turns on, the
error code is stored in the control data completion status ((S1)+1).
For details on the causes of errors, see the User's Manual (Basic).
Create control data at D20 and on
Create send data at D200 and on
ZP.MSEND
"U0"
D20
Processing program when normal completion
Processing program when abnormal completion
E-mail sending
2)
MELSEC-Q/L
D200
M10
MSEND
3)
1 scan
Abnormal
completion
2 - 16