6 DEDICATED INSTRUCTIONS
Setting data
Set data
Network number of the local station (1 to 239, 254)
Jn
254: The network designated by the valid module during other station
Start I/O signal of the local station's Ethernet module.
Un
(00 to FE
(S1)
Head device of the local station that stores the control data.
(S2)
Head device of the target station from which data is read.
(D1)
Head device of the local station that stores data read.
Local station device that is turned on for one scan by the completion of
(D2)
the instruction.
(D2) + 1 is turned on if the instruction execution completes abnormally.
Device of the target station that is turned on for one scan by
(D3)
completion of the instruction. (Read notification device)
6 - 47
Description
access.
: The higher 2 digits of the 3-digit I/O signal.)
H
4 The "Set by" column indicates the following:
• User: Data is set by the user before executing a dedicated instruction.
• System: The programmable controller CPU stores the execution result of a
dedicated instruction.
The local devices and the file register for each program cannot be used as devices
used in setting data.
MELSEC-Q/L
4
Set by (
)
Data type
Binary 16 bits
User
Character string
User, system
Device name
User
System
Bit
6 - 47