Mitsubishi Electric Melsec Q Series User Manual page 28

Ethernet interface module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

1 OVERVIEW
Function
Sending character
strings in the e-mail's
When using
main text by the
the e-mail
programmable
function
controller CPU
monitoring function
Specifying target station number in
data link instructions
Specifying target station's CPU type in
data link instructions
Increased data length of data link
instructions (480 to 960 words)
Setting the arrival monitoring time of
the data link instruction in 100ms
increments
1 - 5
(2) Function added for function version D
The programmable controller CPU monitoring function allows
transmission of character string information stored in word
devices by the e-mail's main text.
In the following data link instructions, the target station
number 65 to 120 can be specified. (Specification of the
station number 65 to 120 in the CC-Link IE Controller Network
and CC-Link IE Field Network is available.)
• SEND
• READ/SREAD
• WRITE/SWRITE
• REQ
In the following data link instructions, the target station's CPU
type can be specified ((S1)+3). (Specification of
control/standby system or system A/B in the redundant
system is available.)
• READ/SREAD
• WRITE/SWRITE
• REQ
The data length can be specified up to 960 words in the
following data link instructions:
• SEND
• RECV/RECVS
• READ/SREAD
• WRITE/SWRITE
Using the following data link instructions, arrival monitoring
time can be set in 100ms increments.
• READ/SREAD instructions
• WRITE/SWRITE instructions
1 In a multiple network system, when transferring data exceeding 480 words to a station of
another network No., specify the Q or L series models to all of the request source, relay
station and request target.
Overview
1
MELSEC-Q/L
Reference
section
Chapter 2
Chapter 4
Chapter 6
Chapter 6
1 - 5