Mitsubishi Electric Melsec Q Series User Manual page 243

Ethernet interface module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

APPENDIX
Setting target
Sequence scan time of the CPU module (St)
Communication
request source
Control data for the data link
station
instruction
Communication
request destination
Response time of the CPU module (Rt)
station
Total processing time of the data link instruction (when the instruction is resent by the number of resends)
1 Since the arrival monitoring time value may be rounded off, add "100ms".
Setting target
Sequence scan time of the CPU module (St)
Communication
request source
Control data for the data link
station
instruction
Communication
request destination
Response time of the CPU module (Rt)
station
Total processing time of the data link instruction (when the instruction is resent by the number of resends)
1 Since the arrival monitoring time value (default: 0) is smaller than the TCP resend timer value (default:
10s), the processing time will be the same as the TCP resend timer.
App - 5
(c)
Total processing time of the data link instruction (when the instruction is
resent)
The processing time can be shortened by setting the arrival monitoring time
shorter.
• Setting "100ms" for the setting unit of arrival monitoring time
Item
Arrival monitoring time unit
(bit 8 of (S1) + 0)
Arrival monitoring time
Number of resends
20ms × 2 + 200ms × 3 + 30ms = 670ms
• Using the default for Ethernet module parameter (setting "1s" for arrival
monitoring time unit
Item
Setting unit of arrival monitoring time
(bit 8 of (S1) + 0)
Arrival monitoring time
Number of resends
20ms × 2 + 10s × 3 + 30ms = 30.07s
MELSEC-Q/L
Setting value
Processing time
-
In increments of 100ms
(1)
1
2
3
-
Setting value
Processing time
-
In increments of 1s
(0)
0
3
-
20ms
-
200ms
-
30ms
670ms
20ms
-
1
10s
-
30ms
30.07s