Upgrading Firmware For A Redundant Controller - Honeywell ControlEdge 900R04-0200 Getting Started

Plc and rtu
Table of Contents

Advertisement

Chapter 5 - Operating
72
9.
After the application has been upgraded, enter the password to re-
connect the controller.
10.
Click
to complete the firmware upgrade.
OK

Upgrading firmware for a redundant controller

ATTENTION: It is recommended to upgrade the firmware
without opening a project.
There are two procedures for the firmware upgrade of an redundant
controller.
: The primary CPM is synced with the secondary CPM.
On-process
n
ATTENTION: On-process is ONLY applicable for upgrading
R150 to later release firmwares.
: The primary CPM is not synced with the secondary
Off-process
n
CPM.
For ControlEdge 900 Controller, it is ONLY allowed in
or
Running
Stop Locked
You can rotate the mode switch on CPM to change the operating
mode, see "CPM mode switch" in ControlEdge 900 Platform
Hardware Planning and Installation Guide. If the mode switch is in
the REMOTE position, See "Setting operating modes" on page 1
for more information.
Prerequisites
Assume the primary CPM is at slot A and the secondary CPM is at
n
slot B.
Both primary (slot A) and secondary (slot B) CPMs are powered
n
on.
To upgrade the firmware with On-process procedure
ATTENTION: For ControlEdge 2020 controller, on-process
procedure is ONLY applicable for a standalone redundant
controller without EFM configured and IOM connected.
1.
From the Start Page, click
CPM (slot A).
2.
From the Home Page, select
operating mode.
to connect the target primary
Connect
Upgrade Firmware
Stopped,
under
,
Maintenance