Chapter 6 - Communication
Configuring CDA
106
CDA is short for Control Data Access. CDA protocol supports peer to
peer communication between ControlEdge 900 controller with C300
controller or ACE or SIM-300 or SIM-ACE. ControlEdge 900
controller acts as the CDA responder and C300 Controller(or the
others mentioned above) acts as the CDA initiator.
It supports:
Maximum 20 CDA initiators connected to a single CPM
n
Maximum 1000 PPS (parameters per second) between CDA
n
initiators and CPM
Both read and write access from C300 or ACE Controller
n
Read access from SIM-300 or SIM-ACE
n
Communication Security including IPsec and embedded Firewall
n
To configure a CDA responder, perform the following steps: