Siemens SIDOOR AT40 System Manual page 136

Automatic door controls
Hide thumbs Also See for SIDOOR AT40:
Table of Contents

Advertisement

Controllers
6.6 Connecting terminals and interfaces
Task
The relay module's relay contacts can be used to report the following door states to the
higher-level controller:
Table 6- 21
SIDOOR AT40/ATD400V/ATD400K/ATD400W door states
Relay
Function
contact
X11
The door has reached the "CLOSED" position
The relay switches on when the controller has detected the CLOSED position and the pulse generator ceases
to output pulses, i.e. the door is stationary. Pin 3 only remains connected to Pin 1 until the "DOOR OPEN"
command is issued. The relay then drops out again immediately, and Pin 3 is once again connected to Pin 2.
X12
Door reverses because of an obstruction, interruption of the light barrier or an opening command.
The relay switches on when the door reverses because of an obstruction, interruption of the light barrier or an
opening command. Pin 1 is then connected to Pin 3 until the OPEN position is reached.
X13
The door has reached the "OPEN" position.
The relay switches on when the distance of the door from the OPEN position falls below 2 cm. Pin 1 and Pin 3
are then connected. The relay drops out immediately as soon as the distance exceeds 2 cm again, and Pin 3
is once again connected to Pin 2.
Table 6- 22
SIDOOR ATD401W door states
Relay
Designation
contact
X11
CLOSE
(closed)
X12
REVERSE
(reversing)
X13
OPEN
X11 and
FAULT
X13
136
Function
The system's internal door state "closed" is signaled via this relay (relay contact is closed).
This state is not only position-dependent. Note the following conditions:
The "closed" state can only be achieved with a drive order
The "closed" state cannot be achieved by external pushing
The "closed" state can be terminated by means of a drive order or external pushing
The relay is additionally influenced by the sensor configuration (parameter p4600). See also
Section Sensors and external sensor interface module (ATD4xxW) (Page 159).
Sensor function test inactive
The control signals that the current drive order's direction is reversed.
Example: automatic reversing due to an obstruction, provided that the applicable revers-
ing response is parameterized.
The relay is active as long as the current drive order is inversed.
Sensor function test active
The "TestOUT" sensor function test signal is output.
The system's internal door state "open" is signaled via this relay (relay contact is closed).
This state essentially depends on the current door position.
The "open" state can be achieved both by means of a drive order and also by external
pushing.
The state can be terminated by means of a drive order or external pushing
There is a fault in the system if both relays are simultaneously active (relay contacts closed).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
System Manual, 06/2016, A2B00096162-AN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents