Installation - Siemens SIDOOR AT40 System Manual

Automatic door controls
Hide thumbs Also See for SIDOOR AT40:
Table of Contents

Advertisement

Controllers

6.5 Installation

6.5
Installation
Requirements
The installation site must fulfill the following requirements:
● Minimum clearance to surrounding parts 1 cm
● Even mounting surface
● Maximum distance from the power supply on account of the cable length:
– SIDOOR NT40 / SIDOOR Transformer: 1.5 m
– Connecting cable to line filter (for SIDOOR ATD400T): 0.5 m
● Maximum distance from the geared motor on account of the cable length:
– In the case of SIDOOR M2, M3, MDG180 DIN EN 45545-2, M4, M5 and MEG250:
– With SIDOOR MDG180. MDG400. MDG400 NMS: 0.5 m / 1.5 m / 5 m / 7 m / 10 m /
126
1.5 m
15 m / 20m
(Length depends on the MDG cable used)
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
System Manual, 06/2016, A2B00096162-AN