Connection To The Power Supply; Fig. 7: Pc100X-A3 Power Supply Connector 'Ps-24V; Table 4: Pc100X-A3 Power Supply Connector - 'Ps-24V; Table 5: Pc100X-A3 Power Supply Connector - 'Ps-Fault - Siemens Cerberus PACE Compact Installation, Mounting

Public address and controlled evacuation
Hide thumbs Also See for Cerberus PACE Compact:
Table of Contents

Advertisement

4
Mounting/Installation
24 V connection to the power supply
4.6 24 V connection to the power supply
34 | 122
The 24 V is required on the digital audio matrix board with DC 24 V power. It is
connected to the power supply via the 'PS-24V' connector. An earth connection to
the cabinet is required for a proper work of the digital audio matrix board. The
power supply reports a general fault status and an AC fault via the 'PS-Fault'
connector. These connectors are located in the inputs/outputs area on the lower
left corner of the board. All connections are pre-assembled.

Fig. 7: PC100x-A3 power supply connector 'PS-24V'

Power supply connector - 'PS-24V'
Pin
Description
1
DC 24 V +
2
DC 24 V 1

Table 4: PC100x-A3 power supply connector - 'PS-24V'

Power supply connector - 'PS-Fault'
Pin
Description
1
Fault
2
AC
3
10 V

Table 5: PC100x-A3 power supply connector - 'PS-Fault'

The power supply fault contact is usually closed and will open in case of a fault.
Earth connector
Pin
Description
1
Earth

Table 6: PC100x-A3 earth connector

Remark
Red
Black
Remark
Function
Green
Power supply fault
Blue
AC 230 V fault
Red
10 V reference voltage to
the power supply
Remark
Function
Yellow/green
Connect to the cabinet earth