Dev-: It is deviation- event. This event will be triggered on the negative deviation of process value.
The job or alarm is activated when the process value is deviated by the value lower than
set point from the previous process value.
For example,
Set point =10
At 10.00.01 Hrs, Tag1=40
At 10.00.02 Hrs, Tag1 = 29
Then, job or alarm is activated.
Error: If there is error in channel input, then alarm or job is actuated
Set point: To set up the process value for actuating Job1 and /or Job2
Hysteresis: To avoid job have been activated too often, option available to set for no reaction in
0.1% to 10% of full span (Low Scale to High Scale).
Job1, Job2: When an event occurs, the task to be performed is called the job. A typical example
is to trigger sound buzzer in event of high temperature. Each pen can accept five
events (or alarms) and each event can create two job
selected
6.2.3.3.5 Jobs
The following jobs are available for configuration to be executed on an event
No Action: Do nothing
Log Alarm (Auto Ack): Record alarm with acknowledgement automatically
Log Alarm: Record alarms
Log Event: Record events
Send Email: Send email if it is configured on an event
Sound Buzzer: Sound the buzzer on an event
DO Latch On: Set digital output / relay on, and then select Target say DO 1. The relay is latched
DO Latch Off: Set digital output / relay off, and then select Target say DO 1. The relay is latched
DO Process: Set digital output / relay on for process high or low, and then select Target from DO
Enable Timer: Start the timer, and then select Target from Timer1 to Timer 100 or all Timers
Disable Timer: Stop the timer, and then select Target from Timer1 to Timer 100 or all Timers
Preset Totalz: Start the totalizer with a preset value, and then select Target from Tolz 1 to Tolz
Reset Totalz: Reset totalizer into zero, and then select Target from Tolz 1 to Tolz 50. It requires
Enable Totalz: Start the totalizer, and then select Target from Tolz 1 to Tolz 50. It requires
Disable Totalz: Stop the totalizer, and then select Target from Tolz 1 to Tolz 50. It requires
:
when it is activated. Digital Output relays will be shown if digital output IO module is
configured and available in database
when it is activated. Digital Output relays will be shown if digital output IO module is
configured and available in database
1 to DO 6. The relay is not going to be latched when it is activated. Digital Output
relays will be shown if digital output IO module is configured and available in
database
50. It requires configuring totalizer via tools and enabling it to appear totalizer
number in the jobs after selecting Preset Totalizer
configuring totalizer and enabling it to appear totalizer number in the jobs after
selecting Preset Totalizer
configuring totalizer and enabling it to appear totalizer number in the jobs after
selecting Preset Totalizer
configuring totalizer and enabling it to appear totalizer number in the jobs after
selecting Preset Totalizer
Page 261 of 479
Various types of jobs can be
s.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pr20Pr30

Table of Contents