Note:
❖ The IO Modules should not be removed or Inserted to the device when the Power is ON. This
should be carried out in the Power OFF Condition only.
❖ For removing the IO Modules, First remove the metal screws then remove the plastic screws, after
that press the lock on the top and bottom of the Card and pull to remove it. Failing to do so will
damage the IO Card. Please follow the Recorder user manual for more information.
❖ The Maximum Torque for the metal screw is 3Kg-cm (2.6in-lb) and the Maximum Torque for the
plastic screw is 0.8Kgf-cm (.7in-lb).
❖ Calibration should be carried out by a qualified Engineer with qualified equipment only.
❖ Thermocouple inputs requires 1 hour initial warm up time during initial setup.
❖ For some industries who prefer circular chart displays, PR30 can offer this Unique feature and set
the display speed for each page/circle in 30 minutes, 1, 2, 4, 8, 12 hours, 1, 2 days, or 1, 2, 4
weeks.

2.4 Wiring

2.4.1 Wiring Precautions

Care must be taken to ensure that the maximum voltage rating specified on the label is not exceeded.
For the panel-mount version, it is recommended that near an external fuse or an external switch rated
at 2A/250 VAC should be used.
Beware not to over tighten the terminals screws. The torque should not exceed 0.4 N-m (3.6 Lb-in or
4.0 Kg F-cm).
With the exception of the thermocouple wires, all wires should be stranded copper conductor with
maximum gauge of 18 AWG.
Connect a grounding conductor with 1.6mm diameter minimum to provide protective grounding prior to
turning on the equipment.