5.1.6.4.3 Method
This is the method of logging measured data. Select the column Method and press Enter. Then
choose the required Log method from the available methods Instant, Average, Minimum or Maximum of
data.
5.1.6.4.3.1 Instant
Logging the last measured data at the logging interval
5.1.6.4.3.2 Average
Logging the averaged of sampled measured data at the logging interval
5.1.6.4.3.3 Minimum
Logging the minimum of sampled measured data at the logging interval
5.1.6.4.3.4 Maximum
Logging the maximum of sampled measured data at the logging interval
5.1.6.4.4 Speed
It is the logging speed (recording speed) of measured data. The available log speeds are as
below.

5.1.6.5 Modbus Register Value Conversion

5.1.6.5.1 Data Type
The data type for logging is 2 byte or 4 byte
2 byte range: 0 to 65535
4 byte range: 0 to 4294967295
5.1.6.5.2 Modbus Register Value Range (M)
The user can configure the Modbus data range low (ML) and high (MH) according to the device
connected.
5.1.6.5.3 Actual Value Range (M)
The user can configure the Engineering unit, Actual value range low (AL) and Actual value range
high (AH) as per the device.
1. 100 msec/dot
2. 1 Sec/dot
3. 2 Sec/dot
4. 5 Sec/dot
5. 10 Sec/dot
6. 15 Sec/dot
7. 20 Sec/dot
8. 30 Sec/dot
9. 1 min/dot
10. 2 min/dot
11. 5 min/dot
12. 15 min/dot
13. 1 hour/dot
14. 2 hour/dot