750-506, 753-506
The 750-506, 753-506 digital output module has 2-bits of diagnostic informa-
tion for each output channel. The 2-bit diagnostic information can then be de-
coded to determine the exact fault condition of the module (i.e., overload, a
short circuit, or a broken wire). The 4-bits of diagnostic data are mapped into
the Input Process Image, while the output control bits are in the Output Proc-
ess Image.
The output modules seize 4 Instances in Class (0x65).
And the output modules seize 4 Instances in Class (0x66).
4 Channel Digital Output Modules
750-504, -516, -519, -531, 753-504, -516, -531, -540
The output modules seize 4 Instances in Class (0x66).
4 Channel Digital Output Modules with Diagnostics and Input Process
Data
750-532
The 750-532 digital output modules have a diagnostic bit for each output
channel. When an output fault condition occurs (i.e., overload, short circuit, or
broken wire), a diagnostic bit is set. The diagnostic data is mapped into the
Input Process Image, while the output control bits are in the Output Process
Image.
WAGO-I/O-SYSTEM 750
DeviceNet
Bit 7
Bit 6
Bit 5
Bit 7
Bit 6
Bit 5
Bit 7
Bit 6
Bit 5
Input Process Image
Bit 4
Bit 3
Bit 2
Diagnostic
Diagnostic
bit S 3
bit S 2
Channel 2
Channel 2
Output Process Image
Bit 4
Bit 3
Bit 2
not used
not used
Output Process Image
Bit 4
Bit 3
controls
DO 4
Channel
4
I/O Modules • 109
Bit 1
Bit 0
Diagnostic
Diagnostic
bit S 1
bit S 0
Channel 1
Channel 1
Bit 1
Bit 0
controls
controls
DO 2
DO 1
Channel 2
Channel 1
Bit 2
Bit 1
Bit 0
controls
controls
controls
DO 3
DO 2
DO 1
Channel
Channel
Channel
3
2
1