5.2.4 Analog Output Modules

The hardware of an analog output module has 16 bits of measured analog data
per channel and 8 bits of control/status. However, the DeviceNet cou-
pler/controller does not have access to the 8 control/status bits. Therefore, the
DeviceNet coupler/controller can only access the 16 bits of analog output data
per channel mapped in Intel format in the Output Process Image.
When digital output modules are also present in the node, the analog output
data is always mapped into the Output Process Image in front of the digital
data.
Each output channel seizes one Instance in the Analog Output Point Object
(Class 0x68).
2 Channel Analog Output Modules
750-550, -552, -554, -556, -560, -585, (and all variations),
753-550, -552, -554, -556
The output modules represent 2x2 bytes and seize 2 Instances in Class (0x68).
4 Channel Analog Output Modules
750-553, -555, -557, -559, 753-553, -555, -557, -559
The output modules represent 4x2 bytes and seize 4 Instances in Class (0x68).
WAGO-I/O-SYSTEM 750
DeviceNet
Instance
Byte Destination
n
n+1
Instance
Byte Destination
n
n+1
n+2
n+3
Output Process Image
D0
D1
D2
D3
Output Process Image
D0
D1
D2
D3
D4
D5
D6
D7
I/O Modules • 113
Remark
Output Value Channel 1
Output Value Channel 2
Remark
Output Value Channel 1
Output Value Channel 2
Output Value Channel 3
Output Value Channel 4