DeviceNet
Configuration / Parametering with the Object Model
4.6.2.1.3 Message Router (0x02):
no attribute, no services
4.6.2.1.4 DeviceNet Object (0x03):
Instance 0:
Attribute
ID
1
Instance 1:
Attribute
ID
1
2
3
4
5
Services:
Service Code
0x0E
0x10
0x4B
0x4C
Used in
Access
Name
buscoupler
rule
required
get
Revision
Used in
Access
Name
buscoupler
rule
Optional
get/set
MAC ID
Optional
get
Baud Rate
Optional
get/set
BOI
Optional
get/set
Bus-Off
Counter
Optional
get
Allocation
Informa-
tion
Allocation
Choice
Byte
Master`s
ID
Service Name
Get_Attribute_Single
Set_Attribute_Single
Allocate_Master/Slave_Connection
Release_Group_2_Identifier_Set
Data type
Description
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation
is based.
Data type
Description
USINT
Node address
USINT
Baud rate
BOOL
Bus-off Interrupt
USINT
Number of times CAN went to
the bus-off state
Struct of:
s. MAC ID of Master (from
BYTE,
Allocate)
USINT
Description
Used to read a DeviceNet Object attribute value
Used to modify a DeviceNet object attribute value
Requests the use of the predefined Master/Slave
connection
Indicates that the specified connections within the
predefined Master/Slave connection set are no
longer desired. These connections are to be released
(deleted)
WAGO-I/O-SYSTEM 750
Default
Value
0x02
Default
Value
0 - 63
0 - 2
0/1
0 - 255
0 - 63, 255
DeviceNet