122 •
I/O Modules
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).and seize 1 Instance in Class (0x68).
DALI/DSI Master Module
750-641
The DALI/DSI Master module has a total of 6 bytes of user data in both the
Input and Output Process Image (5 bytes of module data and 1 byte of con-
trol/status). The following tables illustrate the Input and Output Process Im-
age, which have 6 bytes mapped into each image.
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).
And the specialty modules represent 1x6 bytes output data and seize 1
Instance in Class (0x68).
Input and Output Process Image
Instance
Byte Destination
n
Instance
Byte Destination
n
Instance
Byte Destination
n
C/S
ID
D0
D1
D2
D3
Input Process Image
S
D0
D1
D2
D3
D4
Output Process Image
C
D0
DALI command, DSI dimming value
D1
D2
D3
D4
Remark
Control/Status byte
Command byte
Data bytes
Remark
Status byte
DALI response
DALI address
Message 3
Message 2
Message 1
Remark
Control byte
DALI address
Parameter 2
Parameter 1
Command-Extension
WAGO-I/O-SYSTEM 750