70 •
DeviceNet
Network Architecture
Note
If possible, route the data line separately from all high current carrying ca-
bles.
Further information
For a detailed specification regarding the cable types, please refer to the
INTERNET under: http://www.odva.org.

4.2.1.3 Maximum Bus Length

In the following table, the permitted cable length is represented in dependence of the Baud
rate. Here, a differentiation is made between the maximum length for a transmission using a
thick and a thin cable.
Baud rate
500 kbit/s
250 kbit/s
125 kbit/s
Tab. 4-1: Maximum bus length dependent on the set Baud rate
When specifying the maximum cable lengths, it is made sure that communica-
tion is possible between two nodes located at maximum distance to each other
(worst case).

4.2.2 Cabling

The connection of a WAGO fieldbus node to the DeviceNet bus cable is made
by the supplied 5-pole plug (Multi Connector 231).
Fieldbus
connection
Series 231
(MCS)
Fig. 4-1: Plug assignment for the fieldbus connection
For wiring using a screened cable, the plus is assigned the connections V+, V-
for the voltage supply and with CAN_High, CAN_Low for data transmission.
The 24 V field bus supply is fed by an external fieldbus network power sup-
ply.
Bus length
Thick + Thin Cable
≤ 100 m (328 ft)
L
+
L
Tick
Thin
+ 2,5 • L
≤ 250 m (820,2 ft)
L
Tick
Thin
+ 5 • L
≤ 500 m (1640,4 ft)
L
Tick
Thin
V+
CAN_High
drain
CAN_Low
V-
only
only
maximal
Thick
Thin
Cable
Cable
100 m
100 m
6 m (19,6 ft)
(328 ft)
(328 ft)
250 m
100 m
6 m (19,6 ft)
(820,2 ft)
(328 ft)
500 m
100 m
6 m (19,6 ft)
(1640,4 ft)
(328 ft)
WAGO-I/O-SYSTEM 750
Tap line length
cumulated
39 m (127,9 ft)
78 m (255,9 ft)
156 m (511,8 ft)
DeviceNet