Programmable Input 1-5 Table - Smartgen HGM6100LT SERIES User Manual

Genset controller
Hide thumbs Also See for HGM6100LT SERIES:
Table of Contents

Advertisement

No.
Items
24
Raise Speed Pulse
25
Drop Speed Pulse
26
Oil Pump Control

7.3 PROGRAMMABLE INPUT 1-5 TABLE

Table 9 - Definition Content of Programmable Input 1-5 (All Is Active When Connect To Ground (B-)
No.
Items
0
Not Used
1
High Temperature Shutdown
2
Low Oil Pressure Shutdown
3
Warn Input
4
Shutdown Input
5
WTH STOP by Cool
6
Generator Close Status
7
Mains Close Status
8
Inhibit WTH STOP
9
Inhibit OPL STOP
10
Remote Start
11
Fuel Level Warn
12
Coolant Level Warn
13
Fuel Level Shutdown
14
Coolant Level Shutdown
15
Inhibit Start Auto
16
Remote Control
HGM6100LT Genset Controller
HGM6100LT Series Genset Controller User Manual
Rising speed time is output while the unit entering into hi-speed
warming up.
Dropping speed time is output while the unit entering into stop
idling.
Engine type select Yuchai-LMB. When unit is standby, pump
control output per 30 minutes. If oil pressure is above 100kPa or
output delay is more than 1minute, it will stop output; if unit is in
re-heating state, oil pump control will always output.
If the signal is active after safety run on delay over, genset will
immediately alarm to shutdown.
Only warning, not shutdown if input is active.
If the signal is active, genset will immediately alarm to
shutdown.
During engine running and the input is active, if high
temperature occurs, controller will stop after high speed
cooling; when the input is disabled, controller will stop
immediately.
Connect to auxiliary port of gen load breaker.
Connect to auxiliary port of mains load breaker.
When it is active, high oil temperature stop is inhibited. See
Note3 of Table8 for more information.
When it is active, low oil pressure stop is inhibited. See Note4
of Table8 for more information.
In Auto mode, when input active, genset can be started and
with load after genset is OK; when input inactive, genset will
stop automatically.
Connected to sensor digital input. The controller sends a
warning alarm signal when active.
Connected to sensor digital input. The controller sends a
shutdown alarm signal when active.
In Auto Mode, when the input is active, no matter mains normal
or not, genset won't start. If genset is in normal running, stop
process won't be executed. When input is disabled, genset will
automatically start or stop judging by mains normal or not.
All buttons in panel is inactive except
2018-10-26
Description
Description
Version 1.0
and
Page 26 of 45