7 PARAMETER RANGE AND DEFINITION

7.1 PARAMETER CONTENT AND RANGE TABLE

No.
Items
1
Mains Normal Delay
Mains Abnormal
2
Delay
3
Mains Under Voltage
4
Mains Over Voltage
5
Transfer Delay
6(1)
Start Delay
7(2)
Stop Delay
8(3)
Start Attempts
9(4)
Preheat Time
10(5)
Cranking Time
11(6)
Crank Rest Time
12(7)
Safety On Time
13(8)
Start Idle Time
14(9)
Warming Up Time
15(10)
Cooling Time
16(11)
Stop Idle Time
17(12)
ETS Solenoid Hold
18(13)
Fail to Stop Delay
HGM6100LT Genset Controller
HGM6100LT Series Genset Controller User Manual
Table 7 – Parameter Content and Range
Range
Default
(0-3600)s
10
(0-3600)s
5
(30-60000)V 184
(30-60000)V 276
(0-99.9)s
1.0
(0-3600)s
1
(0-3600)s
1
(1-10) times
3
(0-300)s
0
(3-60)s
8
(3-60)s
10
(1-60)s
10
(0-3600)s
0
(0-3600)s
10
(3-3600)s
10
(0-3600)s
0
(0-120)s
20
(0-120)s
0
2018-10-26
Description
The delay from abnormal to normal or from
normal to abnormal. It used for ATS (automatic
transfer switch) control.
When mains voltage is under the point, mains
under voltage active. When the value is 30,
mains under voltage disabled. Return
difference is 10V.
When mains voltage is greater than the point,
mains over voltage active. When the point is
60000V, mains over voltage disabled. Return
difference is 10V.
It's the delay from mains open to generator
closed or from generator open to mains
closed.
Time from mains abnormal or remote start
signal is active to start genset.
Time from mains normal or remote start signal
is inactive to genset stop.
When engine start failure, it's the maximum
cranking times. When setting crank times out,
controller send start fail signal.
Time of pre-powering heat plug before starter
is powered up.
Time of starter power up each time.
The second waiting time before power up
when engine start fail.
Alarm for low oil pressure, high temp, under
speed, under frequency /voltage, failed to
charge are all inactive.
Idle running time of genset when starting.
Warming time between genset switch on and
high speed running.
Time for cooling before stopping.
Idle running time when genset stop.
Stop electromagnet's power on time when
genset is stopping.
If ―ETS Solenoid Hold‖ set as 0, it is the time
Version 1.0
Page 18 of 45