13.13
MTU ADEC(SAM MODULE)
It is suitable for MTU engine with ADEC (ECU7) and SAM module.
Terminals of controller
Programmable output1
Start relay output
Terminals of controller
CAN_SCR
CAN(H)
CAN(L)
Engine type: Common J1939
13.14
PERKINS
It is suitable for ADEM3/ ADEM4 engine control mode. Engine type is 2306, 2506, 1106, and 2806.
Terminals of controller
Programmable output1
Start relay output
CAN_SCR
CAN(H)
CAN(L)
Engine type: Perkins
13.15
SCANIA
It is suitable for S6 engine control mode. Engine type is DC9, DC12, and DC16.
Terminals of controller
Programmable output1
Start relay output
CAN_SCR
CAN(H)
CAN(L)
Engine type: Scania
HGM6100LT Genset Controller
Table 31 – ADEC (X1 port)
ADEC (X1port)
X1 43
X1 37
Table 32 – SAM (X23 port)
SAM (X23 port)
X23 3
X23 2
X23 1
Table 33 - Connector
Connector
1,10,15,33,34
-
-
31
32
Table 34 – B1 Connector
B1 connector
3
-
-
9
10
2018-10-26
HGM6100LT Series Genset Controller User Manual
Set configurable output 1 as ―Fuel Relay
Output‖.
X1 Terminal 28 Connected to negative of
battery
X1 Terminal 22 Connected to negative of
battery
CAN communication shielding line
Using impedance 120Ω connecting line
Using impedance 120Ω connecting line
Set configurable output 1 as ―Fuel Relay
Output‖.
Connect to starter coil directly
CAN communication shielding line
Using impedance 120Ω connecting line
Using impedance 120Ω connecting line
Set configurable output 1 as ―Fuel Relay
Output‖
Connect to starter coil directly
CAN communication shielding line
Using impedance 120Ω connecting line
Using impedance 120Ω connecting line
Version 1.0
Remark
Remark
Remark
Remark
Page 42 of 45