7.3 DIGIT INPUT 1-5 TABLE (TABLE 3)

Num
Content
0
Not used
1
High Temp. input
2
Low OP alarm input
3
Auxiliary warn input
Auxiliary
4
alarm input
5
Stop after cooled
6
Gens closed input
7
Mains closed input
8
Inhibit WTH STOP
9
Inhibit OPL STOP
10
Remote start input

7.4 SENSOR (TABLE 4)

Num
Temperature
1
Sensor
Pressure
2
Sensor
HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module
After the end of the delay in the safe operation,
if the signal is active, genset will immediately
alarm shutdown.
Auxiliary warn alarm digital input.
shutdown
When power on, if active, genset will shut down
immediately.
During engine running, if the engine occur high
temperature shutdown, when the input is active,
the engine will first initiate cooling delay and
then stop, else will stop immediately.
The input state of genset closed.
The input state of Mains closed.
When it is active, during engine running, if the
engine appears high temperature, the engine
will only send out high temperature warning
alarm, not stop.
When it is active, during engine running, if the
engine appears low oil pressure, the engine will
only send out low oil pressure warning alarm,
not stop.
In automatic state, controller remote starts the
signal effectively when starting.
Content
0 Not used
1 Defined Res. Type
2 VDO
3 SGH(Huanghe sensor)
4SGD(DongKang sensor)
5 CURTIS
6 DATCON
7 VOLVO-EC
8 SGX
0 Not used
1 Defined Res. Type
2 VDO 10Bar
3 SGH(Huanghe sensor)
4 SGD(DongKang sensor)
Description
Defined
resistance
0-999.9 ohm, factory
default is SGX
Defined
resistance
0-999.9 ohm, factory
default is SGX
ISSUE 2011-06-20
Version 1.7
Remark
input
range
is
input
range
is
Page 26 of 34