13.3 CUMMINS QSM11 (IMPORT)

It is suitable for CM570 engine control mode. Engine type is QSM11 G1, QSM11 G2.
Terminals of controller
Programmable output1
Start relay output
Terminals of controller
CAN_SCR
CAN(H)
CAN(L)
Engine type: Cummins ISB

13.4 CUMMINS QSX15-CM570

It is suitable for CM570 engine control module. Engine type is QSX15.
Terminals of controller
Programmable output1
Start relay output
Terminals of controller
CAN_SCR
CAN(H)
CAN(L)
Engine type: Cummins QSX15-CM570
HGM6100LT Genset Controller
HGM6100LT Series Genset Controller User Manual
Table 17 – C1 Connector
C1 connector
5&8
-
Table 18 – 3 Pins Data Link Connector
3 pins data link connector
C
A
B
Table 19 – 50 Pins Connector
50 pins connector
38
-
Table 20 – 9 Pins Connector
9 pins connector
SAE J1939 shield-E
SAE J1939 signal-C
SAE J1939 return-D
2018-10-26
Remark
Set configurable output 1 as ―Fuel Relay
Output‖. Outside expand relay, when fuel
output, making make port 5 and port 8 of C1
be connected
Connect to starter coil directly
Remark
CAN communication shielding line(connect
to ECU terminal only)
Using impedance 120Ω connecting line
Using impedance 120Ω connecting line
Remark
Oil spout switch; Set configurable output 1 as
―Fuel Relay Output‖.
Connect to starter coil directly
Remark
CAN communication shielding line(connect
to ECU terminal only)
Using impedance 120Ω connecting line
Using impedance 120Ω connecting line