Installation; Fixing Clips; Overall Dimension And Panel Cutout - Smartgen HGM6100LT SERIES User Manual

Genset controller
Hide thumbs Also See for HGM6100LT SERIES:
Table of Contents

Advertisement

12 INSTALLATION

12.1 FIXING CLIPS

— The module is held into the panel fascia using the supplied fixing clips.
— Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position.
— Pull the fixing clip backwards (towards the back of the module) ensuring four clips are inside their
allotted slots.
— Turn the fixing clip screws clockwise until they make contact with the panel.
Note: Care should be taken not to over tighten the screws of fixing clips.

12.2 OVERALL DIMENSION AND PANEL CUTOUT

HGM6100LT series controller can be applicable to (8~35) VDC battery voltage. Battery negative
must be reliably connected to engine shell. The connection between controller power (B+ and B-)
and battery (B+ and B-) should not be less than 2.5mm
output line of the charger with battery directly, and then connect battery positive and negative to
power input of controller separately, in case that charger will interfere with the normal running of
controller.
1)
Speed Sensor Input
Speed sensor is installed in the engine for testing flywheel teeth. The connection with controller
uses 2-core screen, shield layer should be connected to terminal16 of controller and the other end
vacant. The other two signal lines are respectively connected to terminal15 and terminal16. At full
speed, output voltage range is (1~24) VAC (RMS), 12VAC is recommended (rated speed). During
installing, make the speed sensor contact the flywheel firstly, then pour out 1/3 laps, finally lock nut
on the sensor.
2)
Output And Expansion Relay
All the outputs of controller are relay output. If need to expand relay, please add freewheeling
diode in both ends of relay coil (when expansion relay coil links DC), or add RC loop (when
expansion relay coil links AC), in case controller or other equipments are interfered.
3)
AC Input
HGM6100LT series controller must externally connect to current transformer; CT secondary
current must be 5A. Besides, the phase of CT and input voltage must be correct, or the sampling
HGM6100LT Genset Controller
HGM6100LT Series Genset Controller User Manual
Fig.8 – Case and Overall Dimensions
2018-10-26
2
. If a float charger is fitted, please connect
Version 1.0
Page 35 of 45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm6120ltHgm6110lt

Table of Contents