No.
Items
13 Low Pressure Warn
14 Input Warn
15 Failed To Charge IN
16 Over Power Warn
17 ECU Warn

5.2 SHUTDOWN ALARMS

When controller detects shutdown alarm, it will send signal to open switch and stop genset. The
alarms are displayed in LCD.
No.
Items
1
Emergency Stop Alarm
2
High Temp. Alarm
3
Low Pressure Alarm
4
Over Speed Alarm
5
Under Speed Alarm
Loss Of Speed Signal
6
Alarm
Genset Over Voltage
7
Alarm
Genset Under Voltage
8
Alarm
9
Genset Over Current
HGM6100LT Genset Controller
HGM6100LT Series Genset Controller User Manual
When the oil pressure of genset is less than threshold and Enabled Low
Oil Pressure Stop Inhibited or Input Low Oil Pressure Stop Inhibited is
active, controller will send warning alarm signal and it will be displayed in
LCD.
When external input is active, controller will send warning alarm signal and
it will be displayed in LCD.
When Failed To Charge input is active, controller will send warning alarm
signal and it will be displayed in LCD.
If over power detection is enabled, when the controller detects that the
over power value (power is positive) has exceeded the pre-set value and
the action select ―Warn‖, it will initiate a warning alarm.
If an error message is received from ECU via J1939, it will initiate a
warning alarm.
Table 5 – Controller Shutdown Alarms
When controller detects emergency stop signal, it will send a stop alarm
signal and it will be displayed in LCD.
When the temperature of water/cylinder is higher than set threshold,
controller will send a stop alarm signal and it will be displayed in LCD.
When oil pressure is lower than threshold, controller will send a stop alarm
signal and it will be displayed in LCD.
When genset speed is higher than set threshold, controller will send a stop
alarm signal and it will be displayed in LCD.
When genset speed is lower than set threshold, controller will send a stop
alarm signal and it will be displayed in LCD.
When rotate speed is 0 and delay is not 0, controller will send a stop alarm
signal and it will be displayed in LCD.
When genset voltage is higher than threshold, controller will send a stop
alarm signal and it will be displayed in LCD.
When genset voltage is under set threshold, controller will send a stop
alarm signal and it will be displayed in LCD.
When genset current is higher than set threshold and delay is not 0, it will
2018-10-26
Description
Description
Version 1.0
Page 14 of 45