Saia-Burgess Controls AG
5.16.1 PCD2.H100, counting module up to 20 kHz
Application
Simple counting module, comprising two inputs "A" and "B" plus one direct control
output marked "CCO"; allows counting of the number of revolutions or the calculation
of distances (pulses) and the measurement by counting of pulses within a logical
AND gate (second input).
Typical areas of application:
● 
Counting revolutions or distances (impulses)
● 
Presetting a count value and switching off output CCO when Counter = 0
● 
Measurement by counting: measuring signals counted only when particular  
conditions are met, e.g. photoelectric barrier covered
● 
Counting with recognition of count direction for incremental shaft encoders  
providing simple motion control
Technical data
Number of systems:
Counting range:
Counting frequency:
Data protection:
Digital inputs
"IN-A" and "IN-B" signal voltages: nominal voltage:
Input current:
Input filer:
Process output
Counter controlled output CCO:
Current range:
Voltage range:
Circuit type:
Voltage drop:
Output delay:
Power supply
External supply
Internal current consumption:
(from +5 V bus)
Internal current consumption:
(from V+ bus)
External current consumption:
Operational conditions
Ambient temperature
Noise immunity:
Manual Manual PCD  1 / PCD  2 Series │  D ocument 26 / 737 EN22  │   2 013-11-26
1
0 ...
65,535 (16 bit) (can be extended with CPU counters)
max. 20 kHz (at pulse/pause ratio 50 %)
All data in this module are volatile
(non-volatile Saia PCD
®
"low" range:
"high" range:
typically 7.5 mA
25 kHz
counter output (switches when count is 0 or 65,535)
5  ...   5 00 mA 
(max. current leakage 1 mA)
(min. load resistance  48 Ω in voltage
range 5  ...   2 4 V).
5  ...   3 2 V smoothed, residual ripple max. 10 %
Electrically coupled, not short circuit protected,
positive switching
typically 2V at 500 mA
< 10 µs,
(longer for inductive load due to
protective diode).
5  ...   3 2 V
, (for supply of CCO output only)
DC
max. 90 mA
0 mA
CCO output load current
operation: 
0  ...   + 55 °C without forced ventilation,
storage:
-20  ...   + 85 °C
EC mark according to EN 61 000-6-3 and EN 61 000-6-2
Input/output (I/O) modules
Fast counting modules
registers are available).
24 V
DC
-30  ...   + 5 V
+15  ...   3 0 V for source operation
5
5-107