Connection concept for temperature sensors
The input signals for the temperature sensors are connected directly to the 10-pole
terminal block (E0  ...   E 7).
The following connection diagram shows a typical layout for tempera-
ture sensors with the PCD2.W340,   ...   W 350 and   ...   W 360 Modules.
●  The reference potential for temperature measurements is the "COM" terminal, 
which should not have any external earth or GND connection.
●  If screened cables are used, screening should be continued to an external 
earthing bar.
●  Unused temperature inputs are to be connected to the logical ground.