4.7.3
RS-232 with PCD2.F520 / F522
The PCD2.F520 and PCD2.F522 modules are only supported by
PCD2.M120  /   M 150  /   M 170  /   M 480 controllers.
RS-232: socket B(1), Port #2, for peripheral device
Peripheral
CTS
RTS
RXD
TXD
SGND
Manual Manual PCD  1 / PCD  2 Series │  D ocument 26 / 737 EN22  │   2 013-11-26
Screw
Cable
terminal block,
socket B/B1
CTS
RTS
RXD
TXD
PGND
Serial interfaces: socket B(1) or B2
PCD2.F520:
1 x RS-232 with RTS  /   C TS and
1 x RS-485 electrically connected
or
1 x RS-232 with RTS  /   C TS and
1 x RS-422 without RTS  /   C TS
for socket B   /   B1  /   B 2
not suitable for modem
PCD2.F522:
choice between
2 × RS-232 with RTS  /   C TS
or
1 × RS-232 full with RTS  /   C TS,
DTR  /   D SR, DCD
Jumper for
2 x RS-232 or
1 x RS-232 full
suitable for modem connection for
socket B   /   B1  /   B