Internal current consumption:
(from V+ bus)
External current consumption:
Terminals:
As the current consumption of this module is considerable, when using a number
of them in the same system, the total load for all modules must be taken into
consideration..
Terminals
9
8
The negative terminals "–" of outputs are connected internally to the ground, each via
a 100 Ω resistor.
Analogue/digital values
Inputs
Input signals
+10 V
+5 V
0 V
-5 V
-10 V
Outputs
Classic
4095
3071
2047
1023
0
Manual Manual PCD  1 / PCD  2 Series │  D ocument 26 / 737 EN22  │   2 013-11-26
U/B0 U/B1
7
6
5
4
3
2
1
0
-A1
+A1
-A0
+A0
-E1
+E1
-E0
+E0
Classic
unipolar
bipolar
4095
4095
2047
3071
0
2047
0
1023
0
0
Digital values
xx7
4095
3071
2047
1023
0
Analogue input and output modules
0 mA
0 mA
Pluggable 10-pole screw terminal block
(4 405 4847 0), for wires up to 1.5 mm²
Bus connector
DC-DC converter
Basic module
Jumper: inputs unipolar (U)
Substitution module
Jumper U/B 0 and U/B 1
on substitution module
Jumper: inputs bipolar (B)
Screw terminals
+ must not be connected
Digital values
xx7
unipolar
bipolar
4095
4095
2047
3071
0
2047
0
1023
0
0
Output signals
Simatic
unipolar
27648
+10.0 V
20736
+7.5 V
13824
+5.0 V
6912
+2.5 V
0
0 V
Input/output (I/O) modules
Simatic
unipolar
bipolar
27648
27648
13824
13824
0
0
0
-13824
0
-27648
bipolar
+10.0 V
+ 5.0 V
0 V
-5.0 V
-10.0 V