SBC PCD1 Series Manual page 233

Hide thumbs Also See for PCD1 Series:
Table of Contents

Advertisement

Saia-Burgess Controls AG
Configuration
Module connections/LED
The connections of the module terminal are the following:
Description of the LED:
Off:
On:
Blinking slow: Channel error (Over range/under range/short circuit/open load)
● 
Blinking fast:  U
How to configure the inputs
Each input channel is configured by a DIP-Switch with four switches. The function of 
each switch is the following:
Switch nr. Off
1
Differential Mode
2
3
4
Gain=1
According to this table, the configuration for the different modes of operation is as fol-
lows:
On
Off
1
2
slider
Voltage mode
0...10 V
How to configure the outputs
Since the outputs are configured by software (with the corresponding FBox or FB), 
there is no need to configure the mode of operation of the outputs with any kind of 
jumpers or DIP-Switches.
Manual Manual PCD  1 / PCD  2 Series │  D ocument 26 / 737 EN22  │   2 013-11-26
Module is not powered. U
Module is running without errors
is lower than specified (< 19 V)
ext
On
Off
3
4
1
2
Current mode
0...20 mA
4...20 mA
Combined analogue I/O modules with galvanic isolation
(24 V) is missing.
ext
On
Single Ended Mode
Current Shunt On
Supply for external Resistors On
Gain=0.25
On
Off
3
4
1
2
Temperature mode
Pt1000 (-50...400 ˚C)
Pt500 (-50...400 ˚C)
Ni1000 (-60...200 ˚C)
Resistor mode
0...2500 Ω
Input/output (I/O) modules
3
4
5
5-97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents