Saia-Burgess Controls AG
Technical data for add-on modules (variant modules)
PCD2.W110
Current sources
Measuring range
Accuracy of measurement better than 0.2 °C
PCD2.W111
Current sources
Measuring range
Accuracy of measurement better than 0.4 °C
PCD2.W112
Current sources
Measuring range
Accuracy of measurement better than 0.2 °C
PCD2.W113
Current sources
Measuring range
Accuracy of measurement better than 0.4 °C
PCD2.W114
Current sources
Measuring range
Accuracy of measurement better than 0.4 °C
Accuracy of measurements
The curves below show the maximum measurement error
(measurement and repeating accuracy).
Total error = linearization error + repeating error
Each channel is calibrated to the minimum and maximum values:
-50 °C
+150 °C
For these two values, the measurement error = 0.
Manual Manual PCD 1 / PCD 2 Series │ D ocument 26 / 737 EN22 │ 2 013-11-26
4 inputs for Pt 100 probes
2 mA
-50 °C ... + 150 °C
4 inputs for Ni 100 probes
2 mA
-50 °C ... + 150 °C
4 inputs for Pt 1000 probes
0.2 mA
-50 °C ... + 150 °C
4 inputs for Ni 1000 probes
0.2 mA
-
-50 °C ... + 150 °C
4 inputs for Pt 100 probes
0.2 mA
0 °C ... + 350 °C
0
+ 2 LSB
→
4095 - 2 LSB
→
Input/output (I/O) modules
Analogue input modules
5
5-55