Saia-Burgess Controls AG
Block diagram
E0
E1
E2
E3
E4
E5
E6
E7
GND
Voltage
Source
10.000 V
..W220 only
Watchdog: This module cannot be used on the base address 240 (or 496 for the
PCD2.M170), because it would interact with the watchdog, and would cause a
malfunction.
Programming examples for the PCD3.W2x0 can be found in a separate manual and on the
TCS Support site www.sbc-support.com.
xx7 and RIOs: the firmware reads in the values according to the configuration (I/O Builder or 
network configurator). 
Watchdog: This module can interact with the watchdog, if it is used on base address 240. In
this case, the last input with address 255 cannot be used.
For details, please refer to the
watchdog in conjunction with PCD3 components.
Manual Manual PCD  1 / PCD  2 Series │  D ocument 26 / 737 EN22  │   2 013-11-26
MUX
7K5
Ref.
Voltage
2.500 V
"Watchdog"
BUSY (adr. 15)
A
DATA OUT
10 bits serial
D
A/D act. (addr. 15)
Clock
Channel address 0.. 7
section, which describes the correct use of the
Input/output (I/O) modules
Analogue input modules
DATA
READ
WRITE
ADDR
+5 V
GND
+24 V
5
5-63