Saia-Burgess Controls AG
LEDs and connection terminals
A3
9
8
7
6
A3
Output circuits and terminal designation
Adress
LED A3
LED
0
1
2
3
Relay energized (contact closed): LED on
Relay reset (contact open):
24 V
must be connected to the +/- terminals.
DC
With an open relay contact, the current leakage through the contact protection is
0.7 mA (at 230 V / 50 Hz). This should be taken into account for smaller AC loads.
If this is too high, it is recommended to use a PCD2.A220 Module (without contact
protection).
Watchdog: This module can be used on all base addresses; there is no interaction with the
watchdog on the CPUs. For details, please refer to the
the correct use of the watchdog in conjunction with PCD2 components.
Manual Manual PCD  1 / PCD  2 Series │  D ocument 26 / 737 EN22  │   2 013-11-26
A2
A1
A0
5
4
3
2
1
0
A2
A1
A0
Output
A0
9
8
A1
A2
A3
24 VDC
Digital output modules, electrically isolated
Bus connector
Bus interface
Relays
Contact protection
LEDs
Screw terminals
Relay contacts
Supply 24 VDC for
Relay coils
7
6
1
A3
A0
Isolated contacts
LED off
"Watchdog"
Input/output (I/O) modules
Contact
protection
Relay
contacts
0
Terminals
section, which describes
5
5-33