SBC PCD1 Series Manual page 192

Hide thumbs Also See for PCD1 Series:
Table of Contents

Advertisement

Saia-Burgess Controls AG
Typical linearity error for W110/112/114 (Pt 100/Pt 1000)
Deviation (LSB)
+6
+5
+4
+3
+2
+1
0
+1
+2
+3
+4
+5
+6
-50
0
Typical linearity error for W111/113 (Ni 100/Ni 1000)
Deviation (LSB)
+6
+5
+4
+3
+2
+1
0
+1
+2
+3
+4
+5
+6
-50
0
On cable break
On short circuit
Base and variant modules
Each module comprises 2 individual modules.
● 
Base module with input filters, A/D converter, I/O port. Same module with same  
fittings for all 4 variants.
● 
Plug-on variant modules with switching circuit to generate -15 V, power sources  
and linearization. Each of the four variants has a module of its own, i.e. a
module with different equipment.
The user has access to the 4 potentiometers to set the offset for each individual
channel. This can be useful for adjusting the zero value (at -50 °C) for long
measurement cables.
All modules are set up in pairs (base and variant module) at the factory. The variant
modules must not be exchanged.
Manual Manual PCD  1 / PCD  2 Series │  D ocument 26 / 737 EN22  │   2 013-11-26
0
+50
1024
2047.5
0
+50
1024
2047.5
Measurement
+100
+150
°C
3071
4095
LSB
Measurement
+100
+150
°C
3071
4095
LSB
Measurement
Measurement
Input/output (I/O) modules
Analogue input modules
4095
0
5
5-56

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents