Saia-Burgess Controls AG
General technical data on inputs and outputs
Resistance to interference:
acc. to IEC 801-4
Internal current consumption:
(from +5 V bus)
Internal current consumption:
(from V+ bus)
External current consumption:
Terminals:
LEDs and connection terminals
9
8
7
6
The module contains 8 LEDs:
●  2 LEDs are directly triggered by the pure inputs. 
●  2 LEDs are directly triggered by the pure outputs. 
●  4 LEDs are triggered by the inputs of the combined inputs/outputs and therefore 
always indicate voltage status at the I/O terminal.
If the combined I/Os are used as outputs, the following should be noted:
The LEDs of combined outputs E/A2  ...   E /A5 only light up when the output is high and 
a supply voltage of 24 V is connected.
Mixing the combined inputs/outputs
If combined I/Os are used as inputs in source operation, i.e. with sending devices
which either apply +24 V to the input or are open, the low status of an open input
can be overwritten as high if the corresponding output at the same address is set
in error. However, if the input is shifted to 0 V with a changeover contact and the
corresponding output is set in error, the MOS-FET can be destroyed, as it is not short
circuit protected. For this reason, only positive-switching contacts should be used.
Manual Manual PCD  1 / PCD  2 Series │  D ocument 26 / 737 EN22  │   2 013-11-26
4 kV under direct coupling
2 kV under capacitive coupling (whole trunk group)
1  ...   2 5 mA 
typically 15 mA
0 mA
Load current
Pluggable 10-pole screw terminal block
(4 405 4847 0), for wires up to 1.5 mm²
5
4
3
2
1
0
Digital combined input and output modules
Bus connector
Bus interface
Output transistors (MOSFET)
Input filter
Recovery diodes
LEDs
Screw terminals
Input/output (I/O) modules
5
5-44

Hide quick links:

Advertisement

Table of Contents
loading