Parameter Descriptions
3-13 Reference Site
Option:
[0]
Linked to
*
Hand / Auto
3
3
[1]
Remote
[2]
Local
3-14 Preset Relative Reference
Range:
0.00
[-100.00 -
%
100.00 %]
*
Illustration 3.22
-100
Illustration 3.23
3-15 Reference Resource 1
Option:
58
VLT
Function:
Select which reference site to activate.
Use local reference when in Hand mode; or
remote reference when in Auto mode.
Use remote reference in both Hand mode
and Auto mode.
Use local reference in both Hand mode and
Auto mode.
NOTE
When set to [2] Local, the frequency
converter will start with this setting
again following a 'power down'.
Function:
The actual reference, X, is increased or
decreased with the percentage Y, set in
3-14 Preset Relative Reference. This results
in the actual reference Z. Actual reference
(X) is the sum of the inputs selected in
3-15 Reference 1 Source, 3-16 Reference 2
Source, 3-17 Reference 3 Source and
8-02 Control Source.
Y
Resulting
Relative
Z
actual
X
Z=X+X*Y/100
reference
Z
X
0
P 3-14
Function:
Select the reference input to be used
for the first reference signal.
3-15 Reference Resource 1,
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up to
three different reference signals. The
MG33ME02 - VLT
®
AutomationDrive Programmming Guide
3-15 Reference Resource 1
Option:
[0]
No function
[1]
Analog input 53
*
[2]
Analog input 54
[7]
Frequency input 29
[8]
Frequency input 33
[11] Local bus reference
[20] Digital pot.meter
[21] Analog input X30-11 (General Purpose I/O Option Module)
[22] Analog input X30-12 (General Purpose I/O Option Module)
[29] Analog Input X48/2
3-16 Reference Resource 2
Option:
[0]
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Frequency input 29
[8]
Frequency input 33
[11]
Local bus reference
[20]
Digital pot.meter
*
[21]
Analog input X30-11
[22]
Analog input X30-12
[29]
Analog Input X48/2
3-17 Reference Resource 3
Option:
Y
100
%
[0]
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Frequency input 29
[8]
Frequency input 33
[11]
Local bus reference
*
[20]
Digital pot.meter
[21]
Analog input X30-11
®
is a registered Danfoss trademark
Function:
sum of these reference signals
defines the actual reference.
Function:
Select the reference input to be
used for the second reference
signal. 3-15 Reference Resource 1,
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up
to three different reference signals.
The sum of these reference signals
defines the actual reference.
Function:
Select the reference input to be
used for the third reference signal.
3-15 Reference Resource 1,
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up
to three different reference signals.
The sum of these reference signals
defines the actual reference.