Parameter Descriptions
NOTE
This parameter cannot be adjusted while the motor is
running.
0-51 Set-up Copy
Option:
Function:
[0]
No copy
No function
*
[1]
Copy to set-
Copies all parameters in the present
up 1
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 1.
[2]
Copy to set-
Copies all parameters in the present
up 2
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 2.
[3]
Copy to set-
Copies all parameters in the present
up 3
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 3.
[4]
Copy to set-
Copies all parameters in the present
up 4
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 4.
[9]
Copy to all
Copies the parameters in the present set-up
over to each of the set-ups 1 to 4.
3.2.7 0-6* Password
0-60 Main Menu Password
Range:
Function:
100
[0 - 999 ] Define the password for access to the Main
*
Menu via the [Main Menu] key. If 0-61 Access
to Main Menu w/o Password is set to [0] Full
access, this parameter will be ignored.
0-61 Access to Main Menu w/o Password
Option:
Function:
[0]
Full access
Disables password defined in 0-60 Main
*
Menu Password.
[1]
LCP: Read only Prevent unauthorized editing of Main Menu
parameters.
[2]
LCP: No access Prevent unauthorized viewing and editing
of Main Menu parameters.
[3]
Bus: Read only Read-only functions for parameters on
Fieldbus and/or FC standard bus.
[4]
Bus: No access No access to parameters is allowed via
Fieldbus and/or FC standard bus.
[5]
All: Read only
Read-only function for parameters on LCP,
Fieldbus or FC standard bus.
[6]
All: No access
No access from LCP, Fieldbus or FC
standard bus is allowed.
If Full access [0] is selected then 0-60 Main Menu Password,
0-65 Personal Menu Password and 0-66 Access to Personal
Menu w/o Password will be ignored.
®
VLT
AutomationDrive Programmming Guide
NOTE
A more complex Password protection is available for OEMs
upon request.
0-65 Quick Menu Password
Range:
200
0-66 Access to Quick Menu w/o Password
Option:
[0]
[1]
[3]
[5]
If 0-61 Access to Main Menu w/o Password is set to [0] Full
access then this parameter will be ignored.
0-67 Bus Password Access
Range:
0
*
®
MG33ME02 - VLT
is a registered Danfoss trademark
Function:
[-9999 -
Define the password for access to the Quick
*
9999 ]
Menu via the [Quick Menu] key. If
0-66 Access to Quick Menu w/o Password is
set to [0] Full access, this parameter will be
ignored.
Function:
Full access
Disables the password defined in
*
0-65 Quick Menu Password.
LCP: Read only Prevents unauthorised editing of Quick
Menu parameters.
Bus: Read only Read only functions for Quick Menu
parameters on Fieldbus and/ or FC
standard bus.
All: Read only
read only function for Quick Menu
parameters on LCP, Fieldbus or FC standard
bus.
Function:
[0 - 9999 ] Writing to this parameter enables users to
unlock the frequency converter from bus/MCT
10 Set-up Software.
3
3
33