Parameter Descriptions
1-33 Stator Leakage Reactance (X1)
Range:
Function:
2.
3.
See Illustration 3.6.
1-34 Rotor Leakage Reactance (X2)
Range:
Function:
Size
[ 0.0400 -
Set the rotor leakage reactance of the
related
400.0000
motor using one of these methods:
*
Ohm]
1.
2.
3.
See Illustration 3.6.
1-35 Main Reactance (Xh)
Range:
Function:
Size
[
1.0000 -
Set the main reactance of the motor
related
10000.0000
using one of these methods:
*
Ohm]
1.
2.
3.
1-36 Iron Loss Resistance (Rfe)
Range:
Function:
Size
[
0 -
Enter the equivalent iron loss
related
10000.000
resistance (R
*
Ohm]
for iron loss in the motor.
®
VLT
AutomationDrive Programmming Guide
measure the value from the
motor.
Enter the X
value manually.
1
Obtain the value from the
motor supplier.
Use the X
default setting. The
1
frequency converter establishes
the setting on the basis of the
motor name plate data.
Run an AMA on a cold motor.
The frequency converter will
measure the value from the
motor.
Enter the X
value manually.
2
Obtain the value from the
motor supplier.
Use the X
default setting. The
2
frequency converter establishes
the setting on the basis of the
motor name plate data.
Run an AMA on a cold motor.
The frequency converter will
measure the value from the
motor.
Enter the X
value manually.
h
Obtain the value from the
motor supplier.
Use the X
default setting.
h
The frequency converter
establishes the setting on the
basis of the motor name
plate data.
) value to compensate
Fe
®
MG33ME02 - VLT
is a registered Danfoss trademark
1-36 Iron Loss Resistance (Rfe)
Range:
Function:
The R
performing an AMA.
The R
in torque control applications. If R
is unknown, leave 1-36 Iron Loss
Resistance (Rfe) on default setting.
1-37 d-axis Inductance (Ld)
Range:
Function:
Size
[
0 -
Enter the value of the d-axis inductance.
related
1000.0
Obtain the value from the permanent
*
mH]
magnet motor data sheet.
This parameter is only active when
1-10 Motor Construction has the value [1]
PM, non-salient SPM (Permanent Magnet
Motor).
For a selection with one decimal, use
this parameter. For a selection with
three decimals, use 30-80 d-axis
Inductance (Ld).
FC 302 only.
1-39 Motor Poles
Range:
Function:
Size related
[2 - 100 ]
Enter the number of motor poles.
*
Poles
~n
@ 50Hz
n
2
2700-2880
4
1350-1450
6
700-960
Table 3.4
The table shows the number of poles for normal speed
ranges of various motor types. Define motors designed for
other frequencies separately. The motor pole value is
always an even number, because it refers to the total
number of poles, not pairs of poles. The frequency
converter creates the initial setting of 1-39 Motor Poles
based on 1-23 Motor Frequency and 1-25 Motor Nominal
Speed.
1-40 Back EMF at 1000 RPM
Range:
Function:
Size
[
10. -
Set the nominal back EMF for the motor
related
9000 V]
when running at 1000 RPM. This
*
parameter is only active when
1-10 Motor Construction is set to [1] PM
motor (Permanent Magnet Motor).
FC 302 only.
value cannot be found by
Fe
value is especially important
Fe
Fe
~n
@60Hz
n
3250-3460
1625-1730
840-1153
39
3
3