Danfoss VLT AutomationDrive FC 300 Series Programming Manual page 23

Hide thumbs Also See for VLT AutomationDrive FC 300 Series:
Table of Contents

Advertisement

How to Programme
Manual initialisation
2
2
1.
Disconnect from mains and wait until the display
turns off.
2.
2a
2b
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
This procedure initialises all except:
15-00 Operating Hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
NOTE
A manual initialisation also resets serial communication, RFI
filter settings (14-50 RFI Filter) and fault log settings.
22
®
VLT
Press [Status] - [Main Menu] - [OK] at
the same time while power up for LCP
102, Graphical Display
Press [Menu] while power up for LCP
101, Numerical Display
MG33ME02 - VLT
AutomationDrive Programmming Guide
®
is a registered Danfoss trademark