Group Objects
8.2

KNX Status Group Objects

Function
1-active
This Group Object cyclically sends an In operation telegram on the bus (ABB i-bus
parameter Sending cycle.
Telegram value:
1 = Active
0 = Inactive
Prerequisite for visibility:
Parameter window General \ parameter In Operation
0-No alarm;
1-Alarm
This Group Object indicates whether there is a communication problem with the server,
Telegram value:
0 = No alarm
1 = Alarm
Prerequisite for visibility:
This Group Object is always visible.
Server Address
This Group Object indicates the server address of the last Modbus server with an error.
Telegram value:
Server Address
Prerequisite for visibility:
This Group Object is always visible.
Register Address
This Group Object indicates the register address of the last Modbus server with an error.
Telegram value:
Register Address
Prerequisite for visibility:
This Group Object is always visible.
Error text
This Group Object is used to set the error text:
Error text: Reports a string signal containing information about the error or alarm. The format of the string is ss:ff:aaaa:ee,
where:
ss: Server ID (00 .. 3F)
ff: Function code (00 .. 10)
aaaa: Address (0000 .. FFFF)
ee: Error code (00 .. 0F)
The following Modbus error codes may occur:
See
The following gateway error codes may occur:
ER0: Unknown error:
The error type cannot be specified.
ER1: CRC error:
The cyclic redundancy test has identified an error in the response structure.
ER2: Reception length error:
The length of the response is incorrect.
ER3: Reception time out:
No response after timeout.
Prerequisite for visibility:
This Group Object is always visible.
54 9AKK108467A5941 Rev. B | MG/S 11.100.1.1 | EN | Product Manual
Group Object name
Status In Operation [1.011]
Status Error alarm [DPT_1.005]
Status Modbus device error [DPT_8.xxx]
Status Modbus register error
[DPT_12.xxx]
Status Error text [DPT_16.001]
https://www.simplymodbus.ca/exceptions.htm
Data point type
Length
1.011
1 bit
®
KNX). The sending cycle is set in
1.005
1 bit
8.xxx
2 bytes
12.xxx
4 bytes
16.001
14 bytes