Device-Specific Parameters - Pepperl+Fuchs VBG-PN-K30-DMD-S16-EV Manual

As-i 3.0 profinet gateway with integr. safety monitor
Table of Contents

Advertisement

AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
7
st. adr 28
8
reserved
9
node status
10
domain no.
St. adr: status of an address from the list 'node overview':
bit-combination meaning
11
01
10
00
13.5

Device-specific parameters

AS-i Flags
Specifies whether the AS-i flags are sent in the PROFINET diagnostic.
Default: Transmission in the PROFINET diagnostic data.
Download Slave Parameters
Based on this entry the parameter bits can be downloaded for each AS-i slave.
These are then sent to the connected AS-i slave when the AS-i cycle is started.
Sending of the set parameters bits can be disabled with this value.
Default: Sending of the AS-i parameter bits enabled.
Failsafe Behaviour
Setting the master response when an AS-i slave fails.
Clear all bits: Input data are set to 0
Set all bits: Input data are set to F
Retain old value: Input data are left at the last valid value.
Default: Input data are set to 0
Freeze Diagnosis
The diagnostic data are continuously updated during runtime. If this is not de-
sired, this parameter can be used to disable continuous updating. Updating then
takes place only when this is required by the PROFINET standard.
Input Data Filter
Filtering of the input data by the specified number of AS-i cycles.
Default: No filtering of the input data.
102
st. adr 27
st. adr 31
node address
manager adr
active
not active
nicht taught (only the manager, with the highest priority message)
not used
(standard)
hex
.
hex
hex
st. adr 26
st. adr 25
st. adr 30
st. adr 29
Tab. 13-39.