Function and startup of the Safety Monitor
10.6.1

Procedure for configuring and teaching code sequences

The configuration is created using ASIMON 3 G2 software, loaded into the safety
unit and released. The name of the person releasing and the date are stored at
this moment. If code sequences controlled through the display are newly taught,
this is secured by a PIN to prevent unintended/unauthorized changing of the code
sequences.
Information!
For additional information see section<Replacing a defective safety-configured AS-i
slave>.
A PIN is a 4-digit number and can only be changed from the display, not via
the ASIMON 3 G2 software.
After entering the PIN, the display can be used to start a teaching procedure
for the code sequences. The monitor stops immediately after entering the
PIN. After teaching, the monitor starts after a prompt and acknowledgement
on the display.
Action
Configure and load into Safety
Monitor
Stopping
Releasing
Starting
Teaching code sequences
Changing the password
Changing the PIN
Legend:
"
" = possible;
"–" = not possible
Code sequences for releasing a configuration do not necessarily have to have
been successfully learned. It is also possible to release without code sequences,
which must then be learned at a later time.
Teaching the code sequences is simple to perform:
Using the ESC/Service key (See section <Replacing a defective safety-con-
figured AS-i slave>)
or
Using the display (See section <Operation in advanced display mode>).
68
ASIMON Software
On AS-i Safety Monitor
(only from chip card)
• (only from chip card)
Tab. 10-10.