AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Advanced Diagnostics for AS-i Masters
12.5.5

Self-resetting fuses

Main menu || SETUP || CURRENT LIMIT ||
Thanks to self-resetting fuses in the "1 Gateway, 1 power supply for 2 AS-i cir-
cuits" Gateway version, when there is a short circuit in one of the two AS-i circuits
the other circuit and the Gateway remain operational - the host controller keeps
receiving diagnostic information from AS-i, which also provides meaningful assist-
ance towards rapid troubleshooting.
The fuse resets itself periodically to check if the error is solved. The measured
current value is available as diagnostic information at the field on the display and
at the control level.
12.5.6

AS-i Power24V capable

Main menu || SETUP || ASI POWER ||
Gateways for AS-i Power24V have been developed especially for use in small
systems. They don't need any special AS-i power supply. With a standard 24V
power supply a 50 m line lenght and with an AS-i power supply min. 100 m line
lenght can be realised.
Maximal:
1,3A
current:
0,3A
Current:
0,3A
Current limiting
3,2A
Current limiting
3,2A
AS-i Power
24V geerdet
change
2
2
2