AS-i 3.0 PROFINET Gateway in Stainless Steel
Configuration of AS-i/PROFINET Gateways
Safety Control Status
Length
14 byte I
4 byte O
16 byte I
4 byte O
10.6

Device-specific parameters

AS-i Flags
Specifies whether the AS-i flags are sent in the PROFINET diagnostic.
Default: Transmission in the PROFINET diagnostic data.
Download Slave Parameters
Based on this entry the parameter bits can be downloaded for each AS-i slave.
These are then sent to the connected AS-i slave when the AS-i cycle is started.
Sending of the set parameters bits can be disabled with this value.
Default: Sending of the AS-i parameter bits enabled.
Failsafe Behaviour
Setting the master response when an AS-i slave fails.
Clear all bits: Input data are set to 0
Set all bits: Input data are set to F
Retain old value: Input data are left at the last valid value.
Default: Input data are set to 0
Freeze Diagnosis
The diagnostic data are continuously updated during runtime. If this is not desi-
red, this parameter can be used to disable continuous updating. Updating then
takes place only when this is required by the PROFINET standard.
Input Data Filter
Filtering of the input data by the specified number of AS-i cycles.
Default: No filtering of the input data.
Language
Selection of the displayed language.
Default: no change of the displayed language.
List of Configuration Errors
description
Safety Ctrl/Status (14 OSSD)
Safety Ctrl/Status (16 OSSD)
hex
.
hex
hex
(standard)
Tab. 10-27.
59