AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
Attention!
Safety advisory:
Ensure that the configuration intended for and released for the application is
used!
This can be done by comparing the release codes on the display (See section
<MONITOR CONFIG>):
The safety representative who generated and validated the configuration
stores the release code for the configuration (Complete or Master) stores the
release code for the configuration and approves use of the configuration for
specific equipment.
The person performing the startup reads out the release code on the display
before starting the equipment or before teaching the code sequences in the
case of master configurations and compares it with the release code released
for the equipment.
After the chip card has been used to load the configuration into the device, the
safety functions of the device must be checked in the equipment.
Checking of the release code and testing the system must be documented in wri-
ting and is part of the system documentation.