Diagnostics

Directly on the device
If a group member does not receive the expected messages from another mem-
ber, it displays the device address of the missing Gateway together with the mes-
sage "not active".
e.g. missing data telegrams from Devicer 4:
About ASIMON
The ASIMON software can be used at any time to perform diagnostics for the
Safe Link by invoking "Safe Link diagnostics" from the "Start diagnostics" menu in
the "Applications" section. This opens a window with a graphical detailed view of
the state of communication for all group members.
If an error occurs in Safe Link, the corresponding signals are shown in gray in the
ASIMON configuration, and at the same time a popup window opens automatical-
ly with a reference to missing devices.
Clicking on the "Safe Link diagnostics" button [1] on the bottom edge of the pop-
up window also opens the diagnostics window for Safe Link.
X.4 not active
[1]
115