Release Circuits; Wiring Overview - Safety Unit - Pepperl+Fuchs VBG-PN-K30-DMD-S16-EV Manual

As-i 3.0 profinet gateway with integr. safety monitor
Table of Contents

Advertisement

AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection
9.9

Release circuits

9.9.1

Wiring overview - safety unit

1.13
0 V
2.Y2
Aux
1.Y1
2.Y1
K1
K3
+1
1.Y1
1.14
3.14
1.Y1 (EDM 1/Start 1), 2.Y1 (EDM 2/Start 2), 1.Y2 (EDM 3/Start 3),
2.Y2 (EDM 4/Start 4)
The safety unit provides 4 inputs. The EDM & START inputs can be defined freely.
The inputs may not be connected to other potentials, but rather only directly or
through potential-free switches to + (for EDM/START).
Switching current static 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 µs).
3.14, 4.14
Semiconductor outputs. Max. contact load: 0.5 A DC-13 at 30 V.
1.13, 1.14; 2.13, 2.14
Potential-free relay contacts. Safety relay with one contact set for read-back. Max.
contact load: 3 A AC-15 at 30 V, 3 A DC-13 at 30 V.
0 V, 24 V
Semiconductor outputs are powered by separate 24 V DC.
+1, +2, +3, +4 (for EDM/Start)
Output supply, powered by AS-i. May not be connected to other potentials, but
rather only directly or through potential-free switches to one of the EDM or START
inputs. Voltage 30 ... 15 V
24 V
2.13
+4
+3
2.Y1
1.Y2
2.Y2
K2
K4
+2
1.Y2
4.14
2.14
.
DC