AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
13.4

PROFINET diagnostics

Description of the diagnostic data which are sent via the PROFINET diagnostics
channel.
13.4.1

Channel error codes

Slot chan-
nel
0
AS-i
Master
AS-i Master
0: circuit 1
1: circuit 2
error
error text
type
16
configuration error
17
slave 0 detected
18
no auto address
assignment
19
auto address
assignment availa-
ble
20
configuration mode
21
no normal operation the AS-i master is performing startup
22
AS-i power fail
23
off-line
24
peripheral fault
25
earth fault
26
overvoltage
27
noise
28
duplicate address
help text
the actual configuration found on AS-i
does not match the projected configu-
ration, or the AS-i master performs
startup operations.
there is an AS-i slave with zero
address
automatic address assignment would
not be possible
as soon as an appropriate slave is
connected, its address will be auto-
matically assigned
the AS-i master is in configuration
mode
operations
the AS-i power supply is insufficient
the AS-i master doesn't send tele-
grams on AS-i
at least one AS-i slave reports a
peripheral fault, or the AS-i master
performs startup operations
the AS-i is short-circuited to ground
the AS-i is short-circuited to an higher
potential
the AS-i signals are noisy
at least two AS-i slaves answers on
the same address
Tab. 13-27.