8.3 General Technical Data

Line power supply (L1, L2, L3)
Supply voltage
AC line voltage low/line drop-out:
During low AC line voltage or line drop-out, the adjustable frequency drive continues until the intermediate circuit voltage drops
below the minimum stop level, corresponding to 15% below the lowest rated supply voltage. Power-up and full torque cannot be
expected at AC line voltage lower than 10% below the lowest rated supply voltage.
Supply frequency
Max. temporary imbalance between line phases
True power factor (λ)
Displacement power factor (cosφ) near unity
THiD
Switching on input supply L1, L2, L3 (power-ups)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 480/690 V
maximum.
Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
* Voltage and power dependent
Torque characteristics
Starting torque (constant torque)
Starting torque
Overload torque (constant torque)
*Percentage relates to nominal torque of the unit.
Cable lengths and cross-sections
Max. motor cable length, shielded/armored
Max. motor cable length, non-shielded/unarmored
Max. cross-section to motor, line power, load sharing, and brake *
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Maximum cross-section to control terminals, cable with enclosed core
Minimum cross-section to control terminals
* See for more information
Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
MG16I322
Operating Instructions
Danfoss A/S © 04/2015 All rights reserved.
380–480 V +5%
50/60 Hz ±5%
3.0% of rated supply voltage
> 0.98 nominal at rated load
maximum once/2 min.
Overvoltage category III/pollution degree 2
0–100% of supply voltage
maximum 160% for 1 m.
maximum 180% up to 0.5 s
maximum 160% for 1 m.
500 ft [150 m]
1,000 ft [300 m]
2
1.5 mm
/16 AWG (2 x 0.75 mm
1 mm
0.5 mm
0.25 mm
1)
18, 19, 27
(> 0.98)
< 5%
8
8
0–590* Hz
Unlimited
0.01–3600 s
*
*
*
2
)
2
/18 AWG
2
/20 AWG
2
/4 AWG
4 (6)
1)
, 29
, 32, 33,
PNP or NPN
0–24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
approx. 4 kΩ